7.4.4.60 Pset_ProtectiveDeviceTrippingUnitTypeThermal
7.4.4.60.1 Semantic definition
Information on tripping units that are thermally tripped.
7.4.4.60.2 Applicable entities
- IfcProtectiveDeviceTrippingUnit/THERMAL
 - IfcProtectiveDeviceTrippingUnitType/THERMAL
 
7.4.4.60.3 Properties
| Name | Property Type | Data Type | Description | |
|---|---|---|---|---|
| ThermalTrippingUnitType | IfcPropertyEnumeratedValue | PEnum_ThermalTrippingUnitType | 
 A list of the available types of thermal tripping unit from which that required may be selected.  | 
|
| I1 | IfcPropertySingleValue | IfcReal | 
 The (thermal) lower testing current limit in [x In], indicating that for currents lower than I1, the tripping time shall be longer than the associated tripping time, T2.  | 
|
| I2 | IfcPropertySingleValue | IfcReal | 
 The (thermal) upper testing current limit in [x In], indicating that for currents larger than I2, the tripping time shall be shorter than the associated tripping time, T2.  | 
|
| T2 | IfcPropertySingleValue | IfcTimeMeasure | 
 The (thermal) testing time in [s] associated with the testing currents I1 and I2.  | 
|
| DefinedTemperature | IfcPropertySingleValue | IfcThermodynamicTemperatureMeasure | 
 The ambient temperature at which the thermal current/time-curve associated with this protection device is defined.  | 
|
| TemperatureFactor | IfcPropertySingleValue | IfcRatioMeasure | 
 The correction factor (typically measured as %/deg K) for adjusting the thermal current/time to an ambient temperature different from the value given by the defined temperature.  | 
|
| CurveDesignation | IfcPropertySingleValue | IfcLabel | 
 The designation of the trippingcurve given by the manufacturer. For a MCB the designation should be in accordance with the designations given in IEC 60898.  |